Squirrel Input Type : B

· For Pulse counting

B Inputs detect and count the number of pulses within the set record interval (or period).

  • B inputs can be configured for voltage input or voltage-free contacts. (<1v = low, >4v = high)
  • Two ranges can be set, with either 1 count resolution or 10 count resolution. If set to 10 count resolution and the actual number of counts in a period is e.g. 58,367, this will be recorded as 58.36. Note the reading is truncated, that is no rounding up or down.
  • Type B input applications include flow rate, rain gauge (tipping bucket type), contact closures etc.

Ranges available in the Squirrel data logger:

Min Max Units Resolution
Number of pulses that can be counted in a period
0 65000 Count 1 Count
0 650K KCount 10 Count

Squirrel modules available:

Module Pulse inputs Other inputs
CPU 1 1 State/Event
M11A 4 4 Voltage/Current
M08 8 -

 


Home | Corporate | News | Products | Support | Services | Agents | Contact